Davis C.

Davis C.


Job Checkin

Arrived onsite to customers complaint of no heat and no hot water, found an ignition failure error code. Unit is 1 year old. High winds were happening yesterday, inlet gas pressure is 10.5 inches wc. Manifold pressure on outlet side was jumping all over the place. Spark electrode was 1/8” away from flame sensor like it should be. Spark electrode was sparking. Attempted to adjust fan speed in manual mode, however it would not let me, it stated fan error. This issue is likely a bad fan, we will need to confirm with triangle tube tech support before we swap out the fan motor. Was able to get the boiler to start working again by powering it off for a few minutes. I cannot guarantee that it will continue to work properly. Will contact triangle tube tech support Monday, and call the customer afterwards. November 4th, unit has been running fine for a week now. Checked inlet vent pipe, found a feather and some debris stuck in foam. This is likely what caused the unit to not work last week. Cl