Davis C.

Davis C. Job Checkin

After installing the wet switch and turning power back on we discovered the unit running the fan. After two hours checking wiring and diagnostic work and confirming with tech support we have determined the control board is defective. The outdoor Y terminal disconnected will allow the system to run normal in heating mode but removes cooling entirely. Returned to complete the control board installation. Issues were all addressed, tested wet switch, tested drains with water bottles. No issues are present. Thank you for choosing CPI Plumbing and Heating Inc.


Davis C.

Davis C. Job Checkin

Arrived onsite to install the customers portable air scrubber, installed upstairs near piano, programmed to meet 2000 square feet. Informed customer on how to clean filter. Thank you for choosing CPI Plumbing and Heating inc.


Davis C.

Davis C. Job Checkin

Arrived onsite completed maintenance and safety inspection on the customers Buderus boiler. Pressure is steady at 13 psi which is good. No signs of leaks on the system, boiler is operating correctly in heating and domestic hot water mode, expansion tank is not failed. Flame sensor reads 3.0 micro amps dc, inducer motor is pulling the correct amount of amps. Gas pressure is right around 11 inches WC. Overall no need for repairs at this time, heat exchanger is clean, unit is operating correctly. Cleaned filter on customers ventilation system. Provided pricing for a portable air scrubber, provided pricing for a ductless mini split for the master bedroom. Air scrubber video https://www.youtube.com/watch?v=uWEQfXx35ik Thank you for choosing CPI Plumbing and Heating Inc.


Davis C.

Davis C. Job Checkin

Arrived onsite customer has had their hvac system leak water from attic into the second floor. Issues present, drain pan under indoor unit is very small and is only underneath the ac coil. Issue number two no wet switch is present in drain pan, this would cut off power to the unit if water entered the drain pan. Issue number three current secondary drain pan is tied into the primary drain pan if primary drain backed up, secondary drain would back up as well. Issue four, current drain line has no strapping and is back graded shortly after leaving the unit. Recommend installing a larger drain pan 5ft by 36 inches in size, recommend adding two p traps one for each drain line. Recommend replacing section of primary drain line that is back graded. Recommend running a completely separate secondary drain line, securing primary and secondary drain line every 4 feet confirming that the drains have proper grade ( currently no strapping is present). Secondary drain line would run out of the atti


Davis C.

Davis C. Job Checkin

Arrived onsite customer had informed me that she had a leak. Discovered that it was coming from the temperature and pressure relief valve as it had failed. And the dhw expansion tank had failed also. Presented pricing customer approved the pricing. Performed work. Discovered a small leak on the boiler expansion tank presented pricing customer approved, so I performed the work. After I swapped out those parts I filled the system up to 15 psi, turned power on to the boiler. And had the customer confirm that she had hot water, and had them give a call for heat. Customer informed me that she had hot water, and I watched as a call for heat on the heating side of things was performed. No error codes or failed attempts at a call for heat. Thank you for choosing CPI Plumbing and Heating Inc.


Davis C.

Davis C. Job Checkin

Customer had a complaint of a leaky relief valve. Arrived onsite took a look at the issue discovered that the expansion tank had failed and the relief valve had failed also. This was causing the relief valve to constantly pour out water. Provided pricing to make the repairs. Customer approved so I began work. Removed and replaced both the relief valve and expansion tank after isolating and draining down the system. Opened up all valves and filled the system back to working pressure. Bled any air. Fired up the boiler checked that the DHW was working properly, checked all heating zones as well. Boiler was operating as should discovered that the boiler did not have an approved back flow prevention device, also noticed that the gauge on the top of the boiler had frozen in place, the fill valve to the boiler was not filling at the correct speed, provided pricing for these repairs, these are not required to make the repair for today but I would recommend these additional repairs to keep the


Oly O.

Oly O. Job Checkin

Met w/customer and drew water sample. Water test results Hardness 10 Grains Iron .25 PH 7.5


Davis C.

Davis C. Job Checkin

Arrived onsite to perform annual safety and maintenance inspection on customers Boiler. Did an inspection looking at all components, making sure all measurements were within the correct thresholds, and in good condition. After taking a look around I noticed that the condensate trap was cracked, provided pricing to replace it. Customer signed off so I did the work. This issue is fairly common in Buderus GB124 boilers. Overall boiler is in good condition, and working as it should. Thank you for choosing CPI Plumbing and Heating Inc.