Customer called in because of a sewer Oder inside of the womens restroom. Went through both bathrooms, flushed toilets multiple times, checked for caulking seal around base of toilets, found no issues at this time, when inspecting mens restroom, found that trap primer had been shut off, returned water to primer, attempted to adjust primer, attempt was unsuccessful. Offer was made to perform replacement at this time. Customer declined replacement of trap primer. We inspected both floor drains, found that floor drain is under woman’s restroom was dry. Found that air was being pulled from the floor drain into the room. Had a conversation with the customer and customer stated that the exhaust fans were recently installed. Let customer know that this will cause sewer Oder to be pulled through a dry P trap. Recommendation was made to add water to p-traps occasionally to prevent p traps from drying out. Thank you for choosing CPI plumbing and heating!