Upon arrival I replace the Inducer Motor Boot. The system is operational upon departure.
I arrived to perform a diagnostic service call on an air conditioner. Upon arrival, I pulled the dirty filter. Drain line is clogged causing pan to overflow. Dual cap-39.2/4.9 rated 40/5 OK. Contactor is burnt and pitted. Refrigerant levels:55 suction 39SH. LOW/LEAKING. Gave options. Client wants to do nothing. A/C alone-$4,249 carrier. Whole system7,499 carrier.
I arrived to perform a diagnostic service call on an air conditioner. Upon arrival, I pulled the dirty filter. Drain line is clogged causing pan to overflow. Dual cap-39.2/4.9 rated 40/5 OK. Contactor is burnt and pitted. Refrigerant levels:55 suction 39SH. LOW/LEAKING. Gave options. Client wants to do nothing. A/C alone-$4,249 carrier. Whole system7,499 carrier.
After removing the Bryant air conditioner, I installed a Carrier 13 SEER 3.5 Ton Air Conditioner. Cycled and monitored the system. Operating normally at this time. Included with the installation is a free 1 year service maintenance agreement. Did not get photo of new installation.
I arrived to perform a diagnostic service call on an air conditioner. Lower level unit. Filter clean. Dual cap-34.5/5 rated 35/5 Ok. Refrigerant levels:62/220 21SH. Condenser needs washed due to it being clogged but there is no water source anywhere outside so I’m unable to wash them.
I arrived to perform a diagnostic service call on an air conditioner. This is one is the one that’s causing the water damage. Found a couple registers with no insulation at all around them and the insulation on the flex ducts coming off of main trunk line are starting to fall apart which is making them sweat and cause the water damage. Client will add new insulation himself. Flushed drain line. Dual cap-34.6/5 rated 35/5 OK. Refrigerant levels:70/241 32SH. Condenser needs washed due to it being clogged but there is no water source anywhere outside so I’m unable to wash them. System appears to be low but coil will first need to be cleaned to confirm readings. Options if system is low after condenser is washed. Fill. Easy seal. Leak search. Replace. Customer will let me know.
I arrived to perform a diagnostic service call on an air conditioner. First floor unit. Removed clogged filter. Found a lot of water in blower cabinet. Evap starting to freeze. Blower cap-13.5/15 LOW. Dual cap-59.8/5 rated 60/5 OK. Refrigerant levels:40/226 60SH. Condenser needs washed due to it being clogged but there is no water source anywhere outside so I’m unable to wash them. System appears to be low but coil will first need to be cleaned to confirm readings. Options if system is low after condenser is washed. Fill. Easy seal. Leak search. Replace. Customer will let me know what they decide if it comes down to it.
I arrived to a diagnostic service call. Found Tstat wired incorrectly and this Tstat does not work with this system. Wired a different Tstat that client provided. Found low voltage fuse blown/replaced. Blower-5.1/7.5. Evap coil is plugged. Dual cap-35/1.1 rated 35/7.5. Replaced both caps and sprayed coil down with rinse free cleaner but it didn’t help much. Running at a 85 suction and 1SH due to dirty coil. Cycled both heating and cooling. All good.
I arrived to a diagnostic service call. Discovered bad nest t-stat/replaced. Board is registering a high limit fault for whatever reason. Reset power a couple times and fault cleared itself. This is a R22 piston. Suction pressure going from 90psig to over 100psig. Evap saturation temp going from 50F to 60F. Evap coil is bad. Client will let me know what he wants to do.
I arrived to perform a diagnostic regarding a unit that was not running properly. Upon inspection I found no low voltage outside. No voltage between R&C or Y&C but transformer is sending out 24V. No low voltage fuse at board. Tapped circuit board a couple times and it started sending out low voltage. Needs a board. Client will fix. 29yrs old. Will have other issues.
I arrived to a diagnostic service call. Upon arrival I discovered filter needs changed. Dead cap/replaced. Washed unit. Compressor-7.6 rated 14.7. Fan-1.4 rated 1.3 over amping and sounds terrible, will fail soon. Condenser coil is literally starting to crumble. Refrigerant levels:73/246 20SH and dropping. 21yrs old system is at the end of its life. All good for the time being.