2330 Indian Springs Rd
Dudley, NC 28333
(919) 734-9611

Our Top Cities


Local Reviews
for ayden, nc

Rated 4.9 out of 5 stars based on 18 customer reviews

Very Good

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Great!

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Great!

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

All should be under warranty

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Great service as always

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Wonderful Experience

Great experience with Jackson and Sons, Will Moreno was on top of his game. Very polite, knowledgeable, thorough and professional. Could not have been more impressed.

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

very good sevice service person was excellent

always great service

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Great service

Perfection

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Great Service!

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Service

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

KEEPS MY SYSTEM RUNNING

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Great service!

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Great Service

Very professional. Best tech we ever had.

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Wonderful service

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Fantastic job by Cuyler

Cuyler did a great job. My mom, Joyce said he was very kind and spent time explaining everything to her.

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Job Locations
for ayden, nc

Kyle W.

Kyle W. Job Checkin

VERIFIED COMPRESSOR IS SHORTED TO GROUND. BUILT ESTIMATE FOR WARRANTY COMPRESSOR REPLACEMENT/MAINTENANCE. WILL CALL WHEN DECISION IS MADE.


Joshua  C.

Joshua C. Job Checkin

Performed routine maintenance per energy savings agreement. Technician was unable to find any challenges while servicing equipment today. The system is heating and cooling properly and holding a delta t of 20 degrees. Customer concern - customer stated that when the heat was on, the downstairs portion of the home was very cold. They said they had to turn it up to 75 in order for it to feel warm downstairs. Technician examined supply temps to both the downstairs and upstairs. Technician found the supply temperatures to be identical. Technician discussed a couple of explanations with the customer for this. 1st is that heat will rise and with the vents being in the ceiling, warm air will tend to stay near the top part of the living space. 2nd is that their new equipment is 2 stage equipment. With the heat being set lower on the 2 stage equipment, the system is not using 100% power to keep the space warm. When they bump the heat up to 74-75, the system is then using full power to heat the


Open T.

Open T. Job Checkin

Tech was unable to open air handler due to electrical box blocking front of unit. Homeowner is going to call electrician to move box so we can access unit. Will call when completed.


Ricardo  T.

Ricardo T. Job Checkin

Tech performed maintenance per energy savings agreement tech found no challenges at today’s visit system is operating correctly at this time. Suggested plasma pure air to homeowner sent estimate is Interested maybe next visit.


Kyle W.

Kyle W. Job Checkin

30+ YEAR OLD ELECTRIC FURNACE BLOWER BEARINGS ARE NOISEY UPON STARTUP. AMP DRAWS/CAPACITOR WITHIN SPECS. DECLINED ALL RECOMMENDATIONS.


Open T.

Open T. Job Checkin

Tech found no difficulties at this time.


Randy K.

Randy K. Job Checkin

Performed scheduled full service maintenance on 8 heat pumps, 1 mini split, changed filters, washed coils, checked capacitors, motor amps, drain traps, heat strips, T-stats.


Romario  T.

Romario T. Job Checkin

Old Oil furnace, system is located in a closet. found a flue pipe rusted out, tech found no voltage going to the W(heat) call from the thermostat, switched from heat to off multiple times from the mercury style thermostat and system intermittently started up heat. Diagnosed a bad thermostat along with a 2 relays, at the oil furnace. Duct work is missing insulation on some branch lines. Due to the flue pipe being rusted out and potential high repair costs, a field supervisor was requested to provide a solution to the homeowner. AC condenser is 20+ years old. System would need to be off for now due to safety purposes. Lunaverena@icloud.com


Juan  R.

Juan R. Job Checkin

25TPA748A003/FV4CNF005L00


Luis R.

Luis R. Job Checkin

Tech found system standing pressures was 71 once system turned on suction drop to 30 psi and low pressure switch cut unit off. Tech informed customer of findings and educated on next steps were to perform leak search and find location of leak. Customer agreed tech found evaporator coil leaking. Tech spoke with office and found warranty had gave out in October of of 2021. Tech informed customer of findings and informed them of potential damages to the compressor due to low refrigerant and moisture. Tech called in a mandatory to give best solution to customer. Tech collected for today’s visit via check.


Noah C.

Noah C. Job Checkin

Upon arrival tech found compressor not running at condensing unit, compressor was in an internal overload. Tech cooled compressor and started system. Tech monitored refrigerant pressures and found suction pressure immediately dropping into the negative. Pressures stayed the same in heat and cool mode. Tech suspects restriction in system. Tech informed customer, customer is going to call company that installed system to come out and make repairs as system is under warranty. Tech collected $87.00 plus tax by card per house call fee.


Kyle W.

Kyle W. Job Checkin

FOUND SYSTEM RUNNING PROPERLY IN BOTH HEATING/COOLING UPONA ARRIVAL. FURTHER INSPECTED FOUND STANDING WATER INSIDE SECONDARY FLOAT SWITCH DUE TO CLOGGED DRAIN LINE. CLEARED DRAIN LINE/TESTED DRAINAGE. SYSTEM COOLING PROPERLY AT THIS TIME. INVESTED IN PSA (1) SYSTEM. SCHEDULE 1ST VISIT. COLLECTED VIA PHONE.


Matthew L.

Matthew L. Job Checkin

Customer reports master bedroom being too cold in the winter time. Also reports house is 68 or 69 degrees when set on 66 on 100 degree days. Tech uploaded pictures of entire duct system. Duct is all intact and no insulation is missing. It is almost fully sheet metal and may be original to older house. Tech found no supply or return air leakage or missing insulation. Bedroom that is too cold is fed from the smaller of the two supply trunks exiting furnace supply side. The smaller branch travels 270 degrees behind and to the side of the furnace. Supply temperatures from the two bedroom vents are 129 and 127 degrees. Bedroom across the hall is 134. Living room is 135. Tech recommends improving attic insulation and focusing insulation on the corner of attic above master bedroom. We can also provide a free quote on duct redesign and replacement or adding a mini split to master bedroom. No housecall per Premium agreement. Uploaded pictures.


Open  T.

Open T. Job Checkin

-Performed Cma inspection on split systems at 7 locations and 1 mini split system. -Hiding house: Outdoor fan capacitor tested weak. Provided estimate for replacement $202.56. -Orchard house: Outdoor fan capacitor tested weak. Provided estimate for replacement $202.56. -Martha’s House: Found EZ Trap installed at air handler drain line on all systems except Martha’s House & Beula Land locations. Recommend installation of EZ Trap to properly clean drain line trap at future services. provided estimate $138.80 per system. -Beula Land: Found EZ Trap installed at air handler drain line on all systems except Martha’s House & Beula Land locations. Recommend installation of EZ Trap to properly clean drain line trap at future services. provided estimate $138.80 per system. -Customer requests to add Luke’s House to future services. -All systems cooling properly at this time.


Romario  T.

Romario T. Job Checkin

Found a failed dual run 40/5 capacitor. Tech received approval for the repairs over the phone by Ms.Phillips. Tech educated the homeowner about ESA(maintenance) but would like to wait on that for now. System is back up cooling. Jtdooley2002@yahoo.com