2330 Indian Springs Rd
Dudley, NC 28333
(919) 734-9611

Our Top Cities


Local Reviews
for newport, nc


Job Locations
for newport, nc

Matthew L.

Matthew L. Job Checkin

Unit is 5 years old. Customer was wanting ballpark to replace multizone mini split (1 condenser with 3 heads) gave ballpark over the phone. Customer will think about it and let us know.


Romario  T.

Romario T. Job Checkin

Tech found no trouble codes on display at the condenser unit or the airhandlers. Compressor did not seem to be operating, system had standing pressures. Tech opened up the compartment for the compressor and checked for ohm values and compared it to LG standards, which checked out okay. Tech cycled the power to reset the system and tested all 3 airhandler heads and it appeared to operate properly. Tech did catch the middle port starting to build up frost but went away after 10 seconds. Stepper motors of EEVs are operating properly, normal range of refrigerant levels were found. Tech turned off the mini split from the control thermostats and started them up in cool twice and system started up without challenges, Costumer has had multiple challenges in the past with this LG multi head mini split every year and is wanting a permanent solution, meaning replacing it with a Mitsubishi brand. Field supervisor will be notified and will provide a solution to the homeowner. Costumer requested to


Bryce C.

Bryce C. Job Checkin

Spoke with customer over the phone customer no longer wanted appointment said the single wide was not worth investing in new package system


Derek J.

Derek J. Job Checkin

Upon arrival tech was told 3 zone mini split was not cooling. Tech leak searched condenser coil and 3 evaporator coils and found no leaks. Searched all flare fitting outside with no leaks found. Tech believes one leak is located behind wall were the flare joint was cut and brazed together. Homeowner only wanted to clean filters and 1 blower wheel due to potentially wanting to replace everything. Tech installed leak freeze and 3.5lbs of R410A to get unit running for the time being.


Matthew L.

Matthew L. Job Checkin

Customer is going to see how long unit will last until replacing. Did not leave quote at this time.


Nate R.

Nate R. Job Checkin

Tech washed and serviced unit and found no challenges at this time. Tech put key back where it was under the condenser.


Noah C.

Noah C. Job Checkin

Performed CMA filter change. Tech replaced and disposed of all existing air filters. Also washed make up air unit filters, photos on file.


David  S.

David S. Job Checkin

-Performed CMA Inspection on 11 split system heat pumps. -Split System 1: Compressor failed megohm test at last maintenance. Windings shorting and compressor likely due for failure. Compressor contactor dark and pitted. Recommend replacement of contactor. 2 pole 30 A. Provided estimate $270.23. Outdoor fan motor amperage slightly high. Outdoor fan motor capacitor tested weak. Recommend replacement of capacitor. Provided estimate $209.77. Observed melted connection at air handler high voltage wiring. Recommend installing split bolts at high voltage wires (3 phase). Provided estimate $172.41. Recommend rewire of heat strips using contactors. Further diagnosis of heat strips should be performed upon approval of wiring repair. System has been recommended for replacement. System should be left off at air handler until wiring repairs may be made or system replaced. -Split System 2: Found proper low voltage on R circuit coming from transformer. Circuit runs to fire alarm junction box then b


Spencer C.

Spencer C. Job Checkin

Tech found thermostat satisfied and system running properly. Refrigerant pressures appeared a little low, but outdoor temperature was 50 and outdoor temp needs to be at least 60 to get accurate pressures, subcooling and superheat measurements. Tech recommends coming back out on a warm day to diagnose refrigerant pressures. Thermostat satisfied at 76, return temp is 76 supply temp is 55. Tech informed customer to keep an eye on it and we will be back in February to do the maintenance


Percy M.

Percy M. Job Checkin

PERFORMED CMA FULL SERVICE ON 2MAKE UP AIR UNITS, 3 GAS PACK UNITS, 6 EXHAUST FANS, 1 DOAS UNIT, AND 2 HEAT PUMP CONDENSERS. ALL SYSTEMS PERFORMING PROPERLY.


Noah C.

Noah C. Job Checkin

Upon inspection of system number 6 tech found low charge as previously found, tech performed leak search on system after approval from Mr. Jeff. Tech found no leaks at evaporator coil or at condensing unit. Tech found lineset leaking at suction line. Looks like lineset is original to building. Will need to get quote to Lumenant to replace approximately 70ft of lineset. System is down for now, tech replaced 5MFD run capacitors on system 2,3, and 7. Billing out for todays visit. Photos on file.


Jesse J.

Jesse J. Job Checkin

Techs preformed CMA FULL SERVICE on 11 split systems. Split System #8 is down due to compressor being shorted to ground, tech recommends replacing system. Split System #1 is operating at this time but compressor failed megohm test, tech recommends replacing system. Split System #6 is down due to low refrigerant possibly caused by leak in Evaporator coil. Maintenance staff asked if system was under any kind of warranty. Tech told office will look into warranty information for system and advise luminant on solution for issue. All other systems are operating at this time but may be in need of minor repairs. Tech has attached estimates to invoice for any minor repairs needed. Tech also attached system performance reports to invoice along with pictures.


Luis R.

Luis R. Job Checkin

Tech was informed living room a/h was hotter then the rest tech did find living room a/h was furthest from condenser once tech turned a/h by its self liquid line would freeze up but when tech would add another a/h head liquid lines would unfreeze tech did that to each individual head and each individual head liquid line would freeze if no other head was on tech added 1lb of refrigerant to the living room head a/h started blowing out 49 degrees like the others tech was unable to get temps below 59 earlier until tech added 1lb tech got approval for leak search tech found a faint detection on upstairs bed room head tech spoke with customer due to how faint detection and tech could not pin point location of leak customer would like to wait to see how long it will take to leak enough to have issues arise again when performing esa in 6 months customer would like leak search again to see if leak is more present


Kyle W.

Kyle W. Job Checkin

FOUND MINI SPLIT HEAD IN MAIN AREA COOLING AT PARTIAL CAPACITY. PERFORMED A FULL RESET OF SYSTEM. CYCLED EACH HEAD WITH PROPER CHANGEOVER AFTER RESET. NO FURTHER CHALLENGES AT THIS TIME.


Matthew L.

Matthew L. Job Checkin

Tech found no 24 volt control voltage inside air handler #9. Confirmed 240 volts into transformer and no voltage out. Terminal on transformer is visibly burnt. Ben Pait approved replacement of transformer so we can further diagnose. After replacing transformer, tech found air handler blowing fuses on a Y call due to low volt coil on 24v 2 pole 40 amp compressor contactor shorted. Uploaded picture of burnt transformer and burnt contactor coil. Tech also found 7.5uf fan capacitor reading low at 5uf. For testing purposes, tech got system running with a new 7.5uf fan capacitor and compressor contactor. Allowed system to stabilize and found subcooling about 1 degree with a design of 15 degrees subcooling. Suction pressure is slightly low. Tech estimates system is 1-2 lbs low on R410a. Bhembree@algsenior.com need to CC. Don McKee approved contactor, capacitor, and refrigerant. After all three components were replaced, tech added 2 lbs of R410a. System is back cooling correctly. Quoted