Jason H.

Jason H.


Job Checkin

No cool. Found compressor overheating due to weak dual Capcitor and dirty condenser coil. Installed turbo dual run capacitor plus Hard start kit with relay and clean condenser coil. Also Perform smiley preventive maintenance inspection on main system courtesy. Will need to call and schedule regular maintenance on both systems has guest house 2 systems total. -Filter: ok Mr replaced has aprilaire media -Flush drain line:with h20 -Installed time release treatment Rec annually -Clean and tighten electrical connections and wires: -Check electrical components: -High voltage wiring stranded -Blower motor: 6.5 amps -Condenser fan motor: .88 amps -Compressor: 11.3 amps -Dual capacitor: 45/7.5 uF Replaced 5 year part warranty -Installed hard start kit 2 year part warranty -Contactor: 228 Volts across -Breaker: amp -Recharge balance refrigerant levels: TXV system Low: 146 psig High: 348 psig super heat: 16'F Sub cool: 9'F -Rinsed out condenser coil -Evaporator c