No cool, Found compressor overheated due to shorted dual capacitor And also system had very low refrigerant levels. Client aware system leaking refrigerant wants temporary fix **No warranty on refrigerant ** Installed new dual cap Flushed and treated drain line Recharge and balance refrigerant levels Low 73 Psig Superheat 5'F High 262 psig Sub Cool 8'F Ck/change filter Measure temperature difference 18'F Indoor temp 75'F Outdoor temp 90'F -Clean and tighten electrical connections and wires: -Check electrical components: -High voltage wiring Romex -Blower motor: 1.4 amps -Condenser fan motor: .9 amps -Compressor: 10.7 amps -Dual capacitor: xx uF -Contactor: 240 Volts across -Breaker: disconnect -Cycle system operating at time ( Waived visit fee with repairs) Client Aware system needs further attention for permanent fix/repair also made aware system can freeze and leak water causing property damage Suggested upgrading equipment 14 years old