3617 Clearview Parkway
Atlanta, GA 30340
770-454-1800

Job Locations
for duluth, ga


Map of Duluth GA
Jason H.

Jason H.


Job Checkin

No cool, Found compressor overheated due to shorted dual capacitor And also system had very low refrigerant levels. Client aware system leaking refrigerant wants temporary fix **No warranty on refrigerant ** Installed new dual cap Flushed and treated drain line Recharge and balance refrigerant levels Low 73 Psig Superheat 5'F High 262 psig Sub Cool 8'F Ck/change filter Measure temperature difference 18'F Indoor temp 75'F Outdoor temp 90'F -Clean and tighten electrical connections and wires: -Check electrical components: -High voltage wiring Romex -Blower motor: 1.4 amps -Condenser fan motor: .9 amps -Compressor: 10.7 amps -Dual capacitor: xx uF -Contactor: 240 Volts across -Breaker: disconnect -Cycle system operating at time ( Waived visit fee with repairs) Client Aware system needs further attention for permanent fix/repair also made aware system can freeze and leak water causing property damage Suggested upgrading equipment 14 years old