Jason was on time - diagnosed the problem quickly - solved it in 30 minutes. Good to have someone reliable and responsive with Christmas company coming into town! Thank you - ed & lucy
Response from RS Andrews:
Thank you for your review!
Water leak, Found drain not connected properly, Relocated to primary and installed Ez tee safety switch Installed time release drain treatment Sealed joints repaired by RSAndrews Flushed out with water Cycled operating properly at time Warranty 1 year on part and 30 days on labor Note system poorly installed Cleints aware drain not properly sealed
Poor cooling, Found drain restricted setting off ez tee safety switch Flushed out drain line with co2 Run 3 gallons of water through drain Monitor refrigerant levels Low 133 Superheat 5 High 313 Sub cool 13 Calibrated u/s stat off 1.5 degrees Measure temp diff 21'F Drop upstairs temp to 72'F from 77'F Outdoor temp 82'F Indoor temp 72'F Cycled system 3 times operating properly at time
Water leak, Found system been leaking for a while emergency drain pan rotted through and evaporator coil coming apart from rust, Also very low refrigerant levels found leak in coil Client aware system leaking refrigerant wants temporary fix till new install on 9/1/16 **No warranty on refrigerant ** Recharge and balance refrigerant Low 71 Psig Super-heat 32 High 228 Psig Sub Cool 25 Ck/change filter Measure temperature difference 18'F Outdoor temp 94'F Client Aware system needs further attention for permanent fix/repair also made aware system can freeze and leak water causing property damage Suggested not to run equipment leaking and rotting of emergency pan Recommend upgrading equipment Temporary fix till installed $425 value with new install
Installed 2 new, 220 volt, dedicated circuits for new HVAC equipment. 1. 50 amp air-handler circuit with disconnect 2. 30 amp heat pump circuit with disconnect. Terminated both wires into panel on correct sized breakers. Left both circuits energized, but left disconnects in off position.
Furnished, wired, and installed a dedicated 40 amp 240 volt feed from the panel to the new location of high temp furnace. Furnished, wired, and installed a plug for said furnace. Performed panel maintenance and tightened all connections. We had to cut Sheetrock. We do not patch. Customer receives a discount as per the Electrical manager.
Technician cut out hole in ceiling and located leak above kitchen, coming from tub drain. Also recommend replacing tub and shower valve stems and handles.
ac unit not cooling turned on ac unit to check out system found system with low suction pressure an high liquid pressure 61/180 with 68.9 degree suction line temp 34 on super heat an 3 degree subcool. cleaned condenser coil an added 2lbs of r22 unit now has a 64/203 pressure with 54 degree line temp 18 degree super heat an 8 on subcool unit seems to be working better now also condonsate pump stop one time but seems to be pumping all out
ONE TIME AC TUNE UP FOR SECOND FLOOR UNIT: Replaced one pleated Filter, Flushed Drain lines, test all electrical components, Test Cooling Mode Check Refrigerant Charge, Rinse Condenser coil with water only. The 2 Ton AC and Coil tempstar is 6 Years Old is not working Properly Due to Poor Maintenance Condition, Low Refrigerant Charge and Dirty Condenser Coil. Note: The gas furnace Lennox is 20 Years Old the Gas line connection is not up to code. Completed repairs by costumer Request. Replaced run capacitor 5.0 uf plus clean condenser coil with chemical and recharged system with 2 pounds of refrigerant R 410 a, test cooling mode is ok. if problem continues on the unit loosing refrigerant I recommend to Performend Electronic Leack search. Air-conditioning inspection Perform smiley preventive maintenance inspection, xx system AC tune up. System 1: Attic System 2: Location -Filter: -Flush drain line: -Clean and tighten electrical connections and wires: -Chec
replaced Kohler class five seal basement bath toilet. replaced fillvalve and supply upstairs daughters bath toilet. installed customer supplied kitchen sink faucet.
Removed failed thermal expansion tank above water heater in basement. Installed new thermal expansion calibrated to confirmed water pressure 60psi. Outside faucets are connected to system before pressure regulator (equal to street pressure pressure). No other plumbing problems found at this time.
Water heater 2/2010 GE Brand Md# SG40T12AVG00/ser#GELN0210A03690 water heater has no thermal expansion tank required by local code.labor and material to Instal $225.90 after hvac discount Water pressure in home 65psi powder room bath o.k kitchen sink drains and faucet o.k garbage disposal needs replacing has excessive rust on mounting collar and disposal itself.labor and material $339.30 upstairs hall bath o.k upstairs master bath toilet needs to pulled from mounting flange and reset do to bolt pulled through flange. labor and material 225.90.left hand lavatory drain slow remove pop-up Assyrian and clean $118.00
Troubleshot GFI in basement by the panel. Found loose wires on the GFI which damaged the GFI. Furnished, wired, and replaced said GFI. GFI works as it should. Performed panel maintenance and tightened all connections. During panel maintenance, found and corrected neutrals bundled up under the same screws. All neutrals and grounds are now separate as they should be. Furnished, wired, and installed surge protection in the panel.
replaced existing burnt out attic fan motor with a new one. set temptation at 105
Water leak Start club 2 system Found system freezing up due to low refrigerant levels and PVC Drain pipe in attic broken Recharge and balance refrigerant levels in both systems Mr aware system leaking refrigerant wants temporary fix **No warranty on refrigerant ** Repair drain line Flush and treated with time release Mr change filters ok Measure temperature difference Indoor temp 83' Outdoor temp 71' Upstairs Low 72 psi High 223 psi Temp diff 22' F Downstairs Low 68 psi High 207 psi Temp diff 21' F Got running can't have installed till 7/13/16 going out of town Cleint Aware system needs further attention to repair Suggested upgrading equipment 18 years old Told will get $500 repair credit if upgrades system within 14 days
fan kicking up high in purge mode. reset purge mode to %25