Conducted electrical inspection for new home addition. Verified grounding electrode system with two 8-foot copper ground rods interconnected per NEC 250.53(A)(2). Checked NM cable stapling at 4.5-foot intervals and appropriate box fill. Confirmed GFCI protection for all required outlets. Tested AFCI circuit breakers using integral test buttons. All electrical installations met current NEC requirements before dry walling.