7668 Standish Place
Rockville, MD 20855
(301) 861-0972

Our Top Cities


Local Reviews
for chillum, md

Rated 5.0 out of 5 stars based on 1 customer reviews

Chief Engineer

My service tech was curious and got in and out in a short matter of time. he is a good tech .

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for chillum, md

Dwayne  B.

Dwayne B. Job Checkin

Kitchen Suppression Repair Ansul R-102 3 Gallon Small kitchen behind auditorium: Furnish necessary parts and labor to complete the following repairs per manufacture specifications and code requirements: -- Replace (4) obsolete mesh filters with new baffle filters. Mesh filters are not allowed and do not meet code requirements. NFPA 96 6.2.3.1 – Grease filters shall be listed and constructed of steel or listed equivalent material. 6.1.3 – Mesh filters shall not be used unless evaluated as an integral part of a listed exhaust hood or listed in conjunction with a primary filter in accordance with UL 1046 Suggested for Ansul R-102 3 Gallon Small kitchen behind auditorium: Hood has (4) mesh style filters installed, 19 1/2”x 19 1/2”x 1 3/4” drop in, should be replaced with aluminum baffle style filters. Inoperable Deficiency: Pyro chem 12 gallon: #8 Stainless steel baffle filters need replacement **The MARYLAND HEATH DEPARTMENT gave them a citation** Galvanized filters no longer complai


James C.

James C. Job Checkin


Brian L.

Brian L. Job Checkin

Portable Extinguishers Inspection


Brian L.

Brian L. Job Checkin

Portable Extinguishers Inspection