He was informative, quick, and explained all that would happen, and most of all, wasn't in anyone's way.
Amy 930-11a MUST CALL WHEN ON YOUR WAY 410 913 1942 Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 6 GAL & (1) ANSUL 4.5 GAL Alarm Int: Yes Inoperable Deficiency for Ansul R-102 6 Gallon Main hood: ANSUEL 6 GALLON RESET RELAY INTERLOCKED BUT GAS DOESN'T SHUT OFF Inoperable Deficiency for Ansul R-102 6 Gallon Main hood: ANSUEL 6 GALLON RESET RELAY INTERLOCKED BUT GAS DOESN'T SHUT OFF Inoperable Deficiency for Ansul R-102 6 Gallon Main hood: Ansul 6 gallon Detection line failed to activate due to excessive grease buildup under hood Parts needed to complete repair: 7 Ansul detectors 20ft of conduit 20ft cable 2 corner pulleys 2.5-3 hours labor
09/09 Egirio 9a Kitchen Suppression Repair Ansul R102 3 gallon Back hood: Furnish necessary parts and labor to complete the following repairs per manufacture specifications and code requirements: ANSUL 3 GALLON BACK HOOD -- Remote pull failed, Re-run remote pull cable and conduit Inoperable Deficiency for Ansul R102 3 gallon Back hood: Ansul 3 gallon Rear kitchen hood Control head not activating when system was tested. Pull station and detection line failed to activate system.
02/04 David 8a see staff Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 6 GAL Alarm Int: Yes