JOHN/10-12 Kitchen Suppression Inspection Pyro Chem KKII PCL300 Left side of hood: Semi-Annual Kitchen Inspection Equip. Desc.: PyroChem PCL300
03//9 john 10a 443-975-4928 MUST CALL WHEN ON YOUR WAY Kitchen Suppression Inspection Pyro Chem KKII PCL300: Semi-Annual Kitchen Inspection Equip. Desc.: PyroChem PCL300
Kitchen Suppression Inspection matt/7am-8/see bunny Semi-Annual Kitchen Inspection Equip Desc: Kitchen Inoperable Deficiency: Ansul 12 gallon (Main hood) ** missing break rod** Repaired 3/11/2020 **Exhaust fan not interlocked to fire suppression system** Deficiency: Detection line snapped during inspection due to frayed link line** (LINK LINE RE-RUN 3/11/2020) **Excessive grease buildup on scissor clips (Grill area) 2 new scissor clips installed (3/11/2020) Deficiency: Ansul 12 gallon (Main hood) **Double tank cartridge expired (MFD 04/2006) Replaced 3/11/2020 Ansul 4.5 gallon **101-30 cartridge expired Replaced 3/11/2020
Portable Extinguishers Service Call
Portable Extinguishers Inspection
Annual Inspection Extinguisher Equip Desc: Inspect Exts
Portable Extinguishers Inspection
Portable Extinguishers and Emergency / Exit Lights Inspection