03/9 Tamara 1130-1230p Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 3 GAL Alarm Int: No Inoperable Deficiency for Ansul R-102 3 Gallon: Same deficiency’s remain: *NO EXHAUST FAN INSTALLED* Pre UL 300 push button style ottoman, Upgrade needed. “U-style clips need to be up graded to Scissor clips” *NO ALARM OR BELL INTERLOCKED TO FIRE SUPPRESSION SYSTEM.*