Portable Extinguishers Inspection Annual Inspection Dept: EXTING Equip Desc: (60) EXTINGUISHERS Inoperable Deficiency for 10 lb ABC Column by salad bar: 10lb abc extinguisher (Salad bar) is missing 10lb abc extinguisher (Bakery) outside bread cooler was removed 10lb abc extinguisher (Deli) needs to be mounted 10lb abc extinguisher (Register #1) is due for hydro testing Last 6 year maintenance was performed in 2015 10lb abc extinguisher (Maintenance shop) is due for hydro testing Last 6 year maintenance was performed in 2015 10lb co2 extinguisher (Electrical room) is due for hydro testing Last hydro testing was performed in 2017 10lb abc extinguisher (Rear emergency exit) Door #6 is missing 5lb abc extinguisher (Pharmacy) is due for 6 year maintenance Last hydro testing was performed in 2015 10lb abc extinguisher (Inside elevator room) is missing
Buddy 9-1 (C) 540-207-7684 Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 9 GAL Alarm Int: Yes Deficiency for Ansul R-102 9 Gallon Kitchen: Ansul 9 gallon: Hydro test due on all 3 cylinders MFD 2010 Regulator test due 2010 Duel cartridge 2011