Dwayne  B.

Dwayne B. Job Checkin

06/066 Sch Brian via emal 8 AM see Chef cooking 10 AM Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 6 GAL & (2) ANSUL 3 GAL Alarm Int: Yes Inoperable Deficiency for Ansul R-102 6 Gallon Main hood: Electrical shock hazard on fridge below grill Improper coverage above grill 4ft 2 (1N nozzles) being used Suggested for Ansul R-102 6 Gallon Main hood: Recommended hood cleaning every 3 months (Quarterly) to avoid excessive grease buildup under hood


James W.

James W. Job Checkin


Dwayne  B.

Dwayne B. Job Checkin

brian 202-367-4979 Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 6 GAL & (2) ANSUL 3 GAL Alarm Int: Yes Inoperable Deficiency for Ansul R-102 6 Gallon Main hood: Ansul 6 gallon: ELECTRICAL SHOCK HAZARD on fridge under grill. Note: Electrician needed to interlocked fridge to Ansul system. Inoperable Deficiency for Ansul R-102 6 Gallon Main hood: Ansul 6 gallon: Fryer shifted out of protecting area. Fryer needs to be adjusted so the appliance can be properly protected.


James W.

James W. Job Checkin