brian 202-367-4979 Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 6 GAL & (2) ANSUL 3 GAL Alarm Int: Yes Inoperable Deficiency for Ansul R-102 6 Gallon Main hood: Ansul 6 gallon: ELECTRICAL SHOCK HAZARD on fridge under grill. Note: Electrician needed to interlocked fridge to Ansul system. Inoperable Deficiency for Ansul R-102 6 Gallon Main hood: Ansul 6 gallon: Fryer shifted out of protecting area. Fryer needs to be adjusted so the appliance can be properly protected.