04/08 Sch w Dawnita 9A-12P onsite 8-3 Portable Extinguishers Inspection Annual Extinguisher Inspection Equip Desc: (2) Extinguishers
said 7am Kitchen Suppression Inspection Semi-Annual Kitchen Inspection Equip. Desc.: (2) ANSUL systems: 10.5-gal. & 9-gal. Deficiency: burnt wires in pcu, still. main automan wiring not in approved junction box, k guard no pressure, 20lb co2 due for hydrotest Deficiency for Ansul R-102 9-gallon Rooftop pcu unit: wires still burnt in pcu unit, need electrician to replace Deficiency for Ansul R-102 10.5-gallon Right side end cap: Interlock not working burnt wiring in pcu control filters for pcu need replacement Inoperable Deficiency for Ansul R-102 9-gallon Rooftop pcu unit: PCU Root top level- Trion air purification system: ALL Filters must be replace. 16 filters Deficiency for Ansul R-102 10.5-gallon Right side end cap: Ansul 10.5 gallon Loose wires inside ottoman needs junction box