Performed annual fire extinguisher inspection as per NFPA 10 standards. Examined 30 units, including ABC dry chemical, CO2, and Class K types. Verified proper operating pressure: 195-205 PSI for ABC, 800-900 PSI for CO2. Checked for physical damage, corrosion, and obstructions in nozzles and hoses. Ensured clear visibility and appropriate signage for all units. Conducted breakdown and internal inspection on 5 extinguishers due for 6-year maintenance. Replaced one unit with expired hydrostatic test date. Updated inspection tags and provided comprehensive report to facility manager, detailing findings and recommendations for strategic placement optimization.
Installed new cabinet and fire extinguisher
ANNUAL FIRE EXTINGUISHER INSPECTION AND MAINTENANCE