Ac diagnostic. Arrive and homeowner states that she believes the whole house went through a power surge. She saw the tv turn off and then the ac stopped working. Concerned to hurt equipment so called us out before resting breaker. Findings: Today I find the circuit breaker to be in the blown position. I cycle the unit back on at the circuit breaker while instructing the homeowner how to do so. If the power surge did actually happen then there is a strong chance this blew the breaker. After cycling the unit on I took an amp draw of 11A, Rates load amperage is 12A, due to extreme 90 degree heat load in the home it is to be expected to have high amperage draw at this time. If the ac does this hint again highly suggest to reset circuit breaker before having us come out or we will have to charge a circuit breaker resetting fee. No abnormal measurements taken besides indoor temperature. Temperature drop of 87 to 58F Compressor amperage after running for 15 minutes: 10.4A Outdoor fan ampe