Upon further inspection. Condenser coil is not leaking. The refrigerant leak is at the 1/2” line exiting the compressor. Refer to photos and videos. 70/7.5 mfd capacitor is below tolerance on the HERM side. Compressor read good from megohmeter check. Will talk to managers on next steps.