AC service... Upon arrival I found the outdoor unit run capaster had burned the wire connections. The capacitor was dead with oil leaking out. I replaced the capacitor and rewired the burnt connections. i checked the system charge and amp draw (9.8 compressor/ 1.8 fan)+ super heat and subcooling, along with manufacturer charge chart and system refrigerant cycle is within manufacturer specifications. Customer has elected to sign up with platinum maintenance agreement today. I'm charging for the capacitor and labor less the 15% discount.