Called out due to furnace not turning on. Noticed no line voltage to the furnace. Customer had been completing add on, and knew of a junction box for the furnace power. He tightened connections, and power was restored to the furnace. Noticed very low gas pressure (1.8â€wc), raisesd to 3.4†and verified 47 degree temperature rise. Furnace is operating properly at this time.