Christopher  J.

Christopher J. Job Checkin

Upon inspection found both circuits have bad tank sensors. And circuit 1 has a leak and is completely flat. The bad tank sensors were causing the glycol tank to get too cold and freeze. Replace tank sensors in both circuits. Repair leak in circuit 1, replace filter drier. Perform nitrogen decay test to ensure no leaks. Evac to 500 microns charge system and test for proper operation. **Customer states they are supplying sensors, quoting for repairs and supplies only** John Hobbs Worked on chiller. Replaced all tanks sensors. Repaired leak in circuit 1. Replaced drier. Charged to factory charge. Tested unit. Unit currently running as designed


Christopher  J.

Christopher J. Job Checkin

Worked on chiller. Found both circuits have bad tank sensors. And circuit 1 has a leak and is completely flat. The bad tank sensors were causing the glycol tank to get to cold and this was causing everything to freeze. I left compressor 2 off to prevent damage from current operating conditions.