7908 Rutillio Ct
New Port Richey, FL 34653
(727) 375-2665

Local Reviews
for new port richey, fl

Rated 4.9 out of 5 stars based on 235 customer reviews

  • Overall Experience
  • Quality
  • Price
  • Convenience

Service on Saturday night

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service on time and efficient

They were there when they said they would be and performed the repair extremely well

  • Overall Experience
  • Quality
  • Price
  • Convenience

Prompt service

Prompt service and problem solved quickly. Very happy with service provided over last 12 years.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service, fast and reliable...will continue using Bay Area

  • Overall Experience
  • Quality
  • Price
  • Convenience

Review

  • Overall Experience
  • Quality
  • Price
  • Convenience

They are fantastic.

Outstanding service.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Service call

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service and awesome price

Glen did a wonderful job. Professional and obviously an expert in this business.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent tech kept me informed on everything he was doing

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for new port richey, fl

Jeff M.

Jeff M. Job Checkin

Upon arrival the other company keeps changing fan speed. They already replaced compressor do to noise complaints. At this time the txv is not metering correctly and needs replaced. Also the duct work was not replaced and think there could be issues with it causing smell in the house. I quoted txv and discussed his options at length. I entered equipment info.


Jeff M.

Jeff M. Job Checkin

Upon arrival the homeowner wanted the new NHP stat installed. I explained to him that his house was originally a straight cool and the install parameters were not set up correctly switching it to a heat pump. I installed NHP and reconnected all wires dis connected from previous tech. I started and checked to make sure the heat strip was not coming on. It is cooling and draining at this time. No stat wire needed replaced. STAT SERIAL 1121M090281


Cliff P.

Cliff P. Job Checkin

System off on float switch safety. Cleaned and flushed drain line with shop vac. Added drain tablets and viper pan spray. Restarted and tested drain line and cooling


Jeff M.

Jeff M. Job Checkin

Upon arrival the homeowner said unit would not reach set point. I checked pressures and subcooling. I sealed behind stat. I went into attic to make sure heat strip was on. I noticed a in home beauty shop right below airhandler which is in attic. I removed panels and found hair spray and salon products building up on coil. I suggested a tuneup and have coils cleaned well.


Cliff P.

Cliff P. Job Checkin

Found a bad capacitor. Replaced the capacitor and checked the system.


Cliff P.

Cliff P. Job Checkin

Completed the maintenance inspection.


Cliff P.

Cliff P. Job Checkin

Secondary pan was full and overflowing. The safety switch in pan was set to high in pan and could not shut down system. Both float switches work but primary pan was also plugged not allowing system to drain properly and overflowing into cabinet and Secondary pan. Also system has an external TXV that was pouring water into Secondary pan. The insulation was to loose and was causing that. Note: I checked for a crack in panand could not find one. Unfortunately that doesn't mean there isn't one. At this timewith all the other issues and not finding one we should be good. Drain cleaning ha 90 day warranty, but if it were to fill pan again that would indicate pan is cracked and needing replaced. We offer service agreements to keep system clean and in proper working condition for $207 for a year. Explanation of agreement is in your email Took 25 gallons of water out of system. Note#2 REPLACE FILTERS AND UNPLUG VENT LOUVERS. ALSO LEAVE FAN IN ON POSITION FOR 48 HOURS.


Cliff P.

Cliff P. Job Checkin

mismatched old system needs replaced asap Temporary fix on old system


Marc M.

Marc M. Job Checkin

Advised system in need of replacement, old r22 system. Have dogs and cats, system is extremely dirty and in bad condition and almost impossible to service. System needs to be replaced.


Glen H.

Glen H. Job Checkin

Routine maintenance Functions and performed normally and within parameters Noted 12" supply and return, undersized


Jeff M.

Jeff M. Job Checkin

upon arrival the system was cooling but not keeping up. I did a leak search and found a leak in evaporater coil. I noticed that it was a mismatched system. The AIRHANDLER was a R410A and the older condenser was R22. I explained everything to homeowner that it was mismatched and that Bay Area could not guarantee a coil replacement with mismatched units. I quoted new coil and several new complete matched systems. I could do nothing for unit today.


Jeff W.

Jeff W. Job Checkin

Clear drain and pan. Install float switch. System operating at this time.


Cliff P.

Cliff P. Job Checkin

Found a tripped float switch due to a clogged drain line. Flushed the drain system


Cliff P.

Cliff P. Job Checkin

Found a tripped breaker. Reset the breaker and checked the system. The buss fuses were blowing. The system is pulling 59.5 amps per leg. Which is popping the buss fuses. Will need to return with the fuses and see about upsizing the breaker.


Cliff P.

Cliff P. Job Checkin

Found the electric heater running at the the same time as the air conditioning. Disconnected the low voltage wiring to the heater and tested other wires. Recommend replacing the low voltage wiring as most leads are getting power.