Diag/ system not cooling, arrived and found the new motor wasn’t coming on. Checked high voltage at motor harness and it has correct 240v and checked low voltage at speed selection and there is correct 24v as well. Verified 24v is passing through the factory relay correctly and the relay is working properly as well. Felt motor and it is not hot to the touch. Turned off power and unhooked motor harnesses to verify there is good connections within the terminal block and everything looks good, reconnected and turned back on the power and suddenly the motor came on. Went back through all the steps and verified nothing was different with any of the voltages and to try to figure out why it was working now but not before, it may have been possible the harness connections were loose and when I removed and replaced them they finally made proper connection. Tested system and everything is now coming on, 35/5 dual run capacitor outside is starting to get weaker (reading 33.5 under a load and ca