5402 Tower Rd
Tallahassee, FL 32303
850-562-3132

Job Locations
for tallahassee, fl


Map of Tallahassee FL
Logan W.

Logan W.


Job Checkin

Diag/ blower not spinning, evaporator coil freezing up. Arrived and turned on system and found it is receiving proper high and low voltage signals from thermostat. Checked wiring diagram and traced power for blower coming from terminal CIRC-H on control board. Found correct 120v coming off board and going to blower module, but the motor has failed. Also found the compressor was running outside but when I checked amp draw off wire coming from HERM terminal on motor booster I found there was none. Tested capacitor and found it is completely dead, compressor was only running due to the start capacitor handling the load. Recommended repairs and customer approved. Picked up 1 HP, 115v, 60 Hz OEM blower motor and module from Trane and returned and replaced, as well as the motor booster for the condenser. Tested system and it is working properly at this time, all motors and compressor are operating within factory specs. Found small hose connected to drain line where ptrap is outside which wa