Performed AC clean and tune; inspected the condenser electrical compartment and tested components, sprayed condenser with coil cleaner, cycled the system on and checked pressures and temps 3 degrees of subcooling with a 12 degree temp split also 31 degree evaporator coil. This system appears to be low on charge recommend looking into options. Job complete