Performed the new furnace start up. No gas leaks detected. Combustion readings were normal. No CO detected in the air. Drain is working. High limit passed the safety check. Heat rise was 55°. Unit is heating properly.
Ac start up. Checked wiring from furnace to condenser unit. Found communicating wire not hooked up indoor and outdoor. Hooked up. Hooked up gauges and checked pressures and temps. Found 400psig of nitrogen on system. Dropped nitrogen from system. Hooked up and pulled a vacuum. Dropped to under 300 microns. Dropped charge. Cycled system. Checked pressures and temps. Found system low on charge. Added 8oz of refrigerant. Subcooling and split good. System operating normal at this time. Job complete.
Performed the start up on a new furnace. No gas leaks detected. Gas and exhaust levels are normal. No CO detected in the air. Drain is working. Venting and electrical components are properly installed. Heat rise was 55 degrees. All registers are installed. Unit is operating normally at this time. Job complete.
Performed the start up on a new furnace. No gas leaks detected. Gas and exhaust levels are normal. No CO detected in the air. Drain is working. Venting and electrical components are properly installed. Heat rise was 55 degrees. All registers are installed. Unit is operating normally at this time. Job complete.