AC Diagnostic System: entrance hall Refrigerant Type R410A Metering Device-TXV SP/HP 125.1/256.7 SLT/LLT69.8/83.4 VSAT/LSAT42.8/85.2 SH/SC27/3.1 Outdoor Entering Air Temperature 77 Filter Size(s) 20x25x4(2) Notes: Upon arrival, checked in with Dennis and worked on the house unit for the upstairs first which was having water back up into the pan and overflowing on the side of the house. Located unit in attic and found pan completely filled as well as secondary float switch filled and primary drain line also filled with water. Vacuumed out all the water from the secondary drain pan, blew out primary condensate line using blow out valve to clear clog. Water started to flow out of primary drain pan into drain line. Found that safety switches were not wired in correctly. Wired them to break communication on r terminal when activated. For the system in the dining area, found dirty filters were causing restriction in airflow causing suction pressure to lower and temperature split to be onl