System- Downstairs Approx Age of System: 3 years Refrigerant Type- R410a Metering Device- TXV SP/HP: 102/242 SLT/LLT:41/72 VSAT/LSAT-33/81 Superheat/Subcool-8/9 Outdoor Entering Air Temp- 73 Outdoor Fan FLA- 1.13 Compressor RLA/LRA- 10.69/152.7 Contactor Voltage- 243/24 Capacitor Rating- 68.18/7.28 Indoor Return Dry Bulb Temp- 71 Supply Temp- 52 Temperature Difference- 19 Required Difference- 16 Filter Sizes – 20x30x1,12x24x1 Changed Filters – No. filters are clean Blew out drain line: Yes Notes- Found starting amperage exceeds the manufacturer spec. We currently have a starting amperage of 152.7 and the unit is rated for 135. I recommend adding start capacitor to assist in reducing the starting amperage and help extend the life of the compressor. . . . . . . . . . System- Upstairs Approx Age of System: 3 years Refrigerant Type- R410a Metering Device- TXV SP/HP: 118/245 SLT/LLT: 52/76 VSAT/LSAT-40/82 Superheat/Subcool- 12/8 Outdoor Entering Air Temp- 73 Outdoor


Casey L.

Casey L. Job Checkin

Unit: RTU 10 Replaced the low ambient pressure switch on the high pressure side of the line set. Tested to make sure the fan would kick on after 450 psi and cut out at 250 psi. Low ambient switch is operating as it should at this time. Power has been restored to the unit after repair. Unit has been returned to operational state.


Casey L.

Casey L. Job Checkin

System: RTU 1 Approx. Age of System: Combustible Gas Leak Detection Pipe and fittings leak-free: yes Valves and orifices leak-free: yes Carbon Monoxide Testing Walk-around CO: pass/0 ppm Airside CO: pass or fail/return 0 ppm supply 0 ppm Flue gas CO: pass or fail/22 ppm Ignition and Combustion Delayed ignition: no Flame disturbance: no Flame discoloration: no Motor Amperages and Capacitors Blower motor FLA: 1.70 Induced draft/combustion blower motor FLA: 0.31 Capacitor(s): pass or fail/mfd Temperature Rise Rated: 30-60 Actual: 41 Static Pressures Blower speed/cfm: RP 0.46 /SP 0.18 TESP: Safety Controls Primary limit test: pass Filter sizes: Changed filters: yes or no Scheduled next tune up date: Notes: ________________________________________ System: RTU 4 Approx. Age of System: Combustible Gas Leak Detection Pipe and fittings leak-free: yes Valves and orifices leak-free: yes Carbon Monoxide Testing Walk-around CO: pass or fail/0 ppm Airside CO: pass/r


Larry W.

Larry W. Job Checkin

Heater has a burning smell. Heating repair and maintenance tune up. Diagnose and perform annual heater maintenance service plan on Ruud heating system. Clear drain lines and check furnace on 11 year old HVAC system. Heater maintenance complete which will help lower heating cost for this residential customer. Evaporator coil is leaking. Recommend replacement evaporator coil, leak repair, or new Comfortmaker air conditioning system. Heating system is now ready for cooler weather.


Mark M.

Mark M. Job Checkin

Perform cool tuneup on comfort club member’s Bryant Furnaces.


Olech G.

Olech G. Job Checkin

Performing a heat tune up x 2 on 2 Bryant systems


Olech G.

Olech G. Job Checkin

Performing a heat tune up x 2 on 2 Bryant systems


Olech G.

Olech G. Job Checkin

Performing a heat tune up x 2 on 2 Bryant systems


Olech G.

Olech G. Job Checkin

Ac and heat tune up x1 on a Rheem system


Olech G.

Olech G. Job Checkin

Ac and heat tune up x1 on a Rheem system


Olech G.

Olech G. Job Checkin

Ac and heat tune up x1 on a Rheem system


Alex Z.

Alex Z. Job Checkin

Ac repair


Patience C.

Patience C. Job Checkin

Diagnose faulty Delta faucet.


Patience C.

Patience C. Job Checkin

Locate leak near backflow preventer.