30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for spring, tx


Map of Spring TX
Ken P.

Ken P.


Job Checkin

Diagnostic System: Main Refrigerant Type R410A Metering Device TXV See attached photos Outdoor Entering Air Temperature 85° Notes: Upon arrival system was low on refrigerant. I opened the coil and and applied leak bubbles to coil finding leak in lower right corner. System warranty expires in august, advised Mr Milam to consider replacement since this is a major repair at the end of the systems warranty life, if the compressor or condenser coil next year it will no longer have a warranty and require replacement. Head pressure was high even though system was overall low on refrigerant due to dirty condenser coil. Advised if going through with warranty coil to have condenser cleaned and start kit installed to get as much life possible out of the outdoor unit after warranty expiration. Mr Milam wants to go through with warranty coil, I performed condenser cleaning and installed a start kit today. Also added 2 pounds of refrigerant to keep system cooling over the weekend. If still under 5