Upon arrival found s30 display screen stuck on the Lennox screen. Checked inside unit and found that the commons weren’t tied together, re-did wiring and reset system. Tstat still stuck on screen. Checked output voltage on hub and was reading 1.6. Went to Lennox and got new s30 Tstat and replaced hub and display. Turned system on and system came on. Set Tstat up. Everything is now operational at this time. I do recommend cleaning outdoor coils due to they were clogged. Homeowner said he would take care of it.