Performed preventative maintenance for a Lennox furnace model #G60UH-48C-110-07, serial #5906K00720. I powered the system down and removed the access panels. I removed the old Healthy Climate 64x56 UV bulb and installed a new one. Removed and cleaned carbon off of the flame sensor, cleaned out the burners and burner box. Ensure that there was nothing clogging the pressure switch. Replaced the air filter size 16x25x1. Checked all electrical connections to ensure that they are secure and in good condition. Performed humidifier service. Removed and replaced the #35 water panel. Cleaned out the housing and drain. Powered the system back up and called for heat. Tested the humidifier for leaks and proper operation. Took a combustion analysis test and received the following readings, o2 levels are 13% and the co levels are at 7ppm. The supply temp is at 122°F. The inducer motor amp draw is at 1.2 and the blower motor amp draw is at 5.4. The system is operating properly at this time.