Performed preventative maintenance on Lennox AC system. Replaced 16x25x1 air filter. Tested evaporator coil pan and condensate line for proper drainage. Temperature split is at 20°. This unit has the proper refrigerant charge. Compressor-5.8 RLA Condenser fan motor-0.6 FLA . Both of these readings are within the amperage rating for this unit. System is operating properly at this time and is ready for the season. Lennox condenser- S#1916H06601 M#14ACXS036-230A20 Filter size-16x25x1 *** Customer has signed up for both heat and AC repair& maintenance.