1570 Old York Road
Abington, PA 19001
215-659-4343

Job Locations
for glenside, pa


Map of Glenside PA
Frank B.

Frank B.


Job Checkin

Customer called for no heat on the second floor. Upon inspection I found the boiler low on water pressure below 10psi. Filled boiler to recommended pressure of 18psi. Purged air since water pressure was so low. Tested the system upon completion. System was operating as it should. Continued to performed the preventative maintenance on the boiler. Inspected all the electrical components. Confirmed proper high and low voltages. Performed a combustion analysis on the boiler. System is operating at 84% efficiency with a CO level of 20ppm. Recommend adding an auto fill w/ backflow preventer to maintain water pressure without having to monitor it. Also to replace the pressure/temperature gauge that is rusting as well as has moisture inside the gauge to where you can’t read it. Model #CGA-4-SPDN Serial #CP5432206