Came out today for a condenser not operating. Upon inspection I found that the system was calling for ac but the condenser was not kicking on. I found that the shut down due to high pressure. Once the system stopped operating the homeowner replaced the old filter. I reset the high pressure switch and the system started right away. The condenser coils are clean and in good condition so it is my belief that the air filter was blocking the air flow and caused the system to trip the high pressure switch. I observed the system running for about 15 minutes and the system is operating properly at this time.