On arrival found the system start and observed the outdoor fan motor spinning at a very slow rate. Checked capacitor reading and found that it was well below rated 40/5 MFD. Disconnected low voltage and observed contactor “sticking” as well. Advised homeowner that these parts needed to be changed first to move forward with the preventative maintenance. After repairs, observed condenser fan motor drawing 0.6 amps which is above nameplate (0.5 FLA). Compressor amperage 6.9, rated (14.1 RLA). The indoor unit blower wheel has a slight rattle to it. Pulled blower assembly to inspect for any defects. The wheel is likely off balance slightly which is to be expected on a 2013 heat pump system. Homeowner replaced the 16x20x1 air filter. All(3) banks of the electric heat pack are functional and reading 19.8 amps per bank. Overall, given the parts that could fail Chud will provide a quote to address the outdoor fan motor and fan blade. We can also provide a FREE estimate to upgrade the system a