Today I came to Pauls Okotoks home because the furnace stopped working over night. Upon diagnostic of the 9 year old system I found it to be in fair condition. The inducing motor, gas valve, safety switches and control board Arne all working well within manufacturers specifications. The ignitions system was replaced 2 years ago and is working well. The pressure switches are sticking when the modulating furnace is calibrating itself. The flame sensor has a very low reading. The pressure switches and flame sensor must be replaced. The system is quite dirty and needs to be cleaned. The home is not equipped with a water softener and the water tank is 9 years old. Furnace was running when tech arrived to Paul’s home in okotoks. Tech replaced both pressure switch’s and tested by turning up heat on thermostat and cycle heat on and off several times. Pressure produce for each pressure is sufficient to open and close switches Tech asked about flame sensor and if they wanted that looked at Te