Systems 40/5 outdoor duel capacitor went bad, replaced and system began operating properly. Checked pressures and subcool while here, pressures and subcool are within range (129/335) with a 10° subcool. Manufacturer calls for 10°+/- 3° on subcool. Brushed debris out of interior of system. Outdoor coil is in fair condition though could use a chemical clean. Compressor is operating under the RLA, fan is operating under the FLA. thermostat is sending voltage to fan when not allowing, customer wants to wait for it to go.