Job Checkin

Tested the main level system. The heat strips are functional and pulling 20 amps. The refrigerant pressures are good and the line temperature is good. If the customer wants to heat the house better in these low temperatures (20-degree range) they will have to have an electrician pull 6/2 wire with the ground to the unit and we can install a 10 KW heat kit.