Complete 1 system a/c repair and preventative maintenance check. Diagnosed system. Older a Trane condenser. 2006. Checked startup and found the system lagging. System startup amps are over 20 due to a weak starter. System hits 53 amps then drops to 22 before starting. Recommend replacing start kit.