Mike  S.

Mike S. Job Checkin

Informed that due to I could only perform indoor portion of CTU customer agreed that would be okay and to move forward instead of rescheduling. Tested all components all measured within ratings and specs. Changed filters. Recommend duct cleaning lvl1.


Justin  P.

Justin P. Job Checkin

Upon arrival customer stated unit wouldn't keep up during the night and had completely stopped working this morning. Inspected indoor unit, no problem found. At condenser the condenser fan motor was running compressor was not. Checked voltage across contactor voltage checked out. Checked 35/5 dual run capacitor, fan side was right below manufacturers range and herm side herm side was reading 0. Replaced 35/5 dual run capacitor started unit. Checked Refrigerant levels, Levels were acceptable at this time. Left system in cooling customer confirmed