1412 Greenwood Road
Weatherford, TX 76008
817-596-4808

Our Top Cities


Job Locations
for oak point, tx


Map of Oak Point TX
Blake  B.

Blake B.


Job Checkin

Tech arrived for a service call. Upon arrival the customer mentioned that there was a error code on the thermostat and the system shut down for a couple hours then came back on. The drain was checked and was gargling. The customer had installed the drain line trap and the vent appeared to be in the opposite position. The customer will add one to the other side of the trap. The Delta was 21 degrees. The outside condenser motor was pulling high amperage. The customer would like exact pricing on this part. ECM 142R 1ph, 1/5hp, 230 V, 0.50A, 850RPM. For a Carrier model# 24ANB160A0030030. Serial# 2311E19202. The customer was given a guess estimate. We will pause the call for pricing.