Trane heat pump with air handler installed in 2020. All electrical connections are tight with no corrosion. Ecm blower motor is acceptable. Blower wheel and evap coil are clean. No drain switch installed however, both primary and secondary drain lines are clear. 40/5 dual run capacitor is in range. Condenser fan motor and compressor are acceptable. Refrigerant and airflow levels are in range. Delta T is 15 degrees at furthest supply vent, 17.5 at the closest.