Complete 2 Systems worked on DS Trane Gas Furnace: ho stated system was not coming on. Found the white wire on tstat diconnected. Reconnected wire. Cycled system. System is working properly at this time.
Vented bathfan to exterior wall with side wall cap
Complete 2 Systems Amana HP Split Systems Performed EPA Heating Maintenance US Amana HP Slit System: Checked thermostat and air filter. Checked amp draws on heat strips and blower motor. Checked run cap. Inspected evap coil. Made sure drain line was clear. Checked compressor and cfm amp draws. Tested defrost board. Checked dual cap. Checked pressures. Cleaned condenser coil. System is running great at this time. DS Amana HP Split System. Performed EPA Heating Maintenance Checked thermostat and air filter. Checked amp draws on heat strips and blower motor. Inspected evap coil. Made sure drain line was clear. Checked compressor and cfm amp draws. Tested defrost board. Checked dual cap. Checked pressures. Cleaned condenser coil. System is running great at this time.
Incomplete: Recall: HO said unit with Compressor we installed suddenly started tripping breaker. Ohmed Compressor and It was giving me 14.9,14.9 and 1.5. Unplugged compressor and fan came on. Bad compressor. Need to call in the morning to get new compressor info. Unit Holds 7lbs of 438a