My overall experience with Comfort First A/C has been excellent! The two technicians were quick and responsive to questions.
Routine maintenance on 2 Goodman heat pumps
Complete: 1 System: EPA Maintenance Goodman Split Heat Pump: Air Handler: Checked Amp Draws on the Blower Motor and Heat strips, checked the blower wheel. Inspected Evap coil. Heat Pump: Checked the charge, and the capacitor. Check the Amp draws on the fan and compressor. Cleaned Unit. System looks good and running Great at this time.
Complete: 2 systems worked On US unit Payne split HP: HO said started freezing up about a month ago. At the HP found system a little low in refrigerant. But when I reversed to heat mode it dropped significantly. Found the outdoor piston but was barely on. Did a quick leak search and then I pumped system down and clean outdoor piston and filter and tightened nut. Pulled vacuum and added 2lbs of 410a. System is working great at this time.
Replacing a start assist on a Trane heat pump
Incomplete: Came to change out zone board. Once I got the new zone board on everything was working except for the US damper would close. Checked voltage going to the motor and motor would not close. Need new motor free of charge per jimmy. Ordering from EC app
Complete two systems, Goodman heat pumps, upstairs system. Found bad dual capacitor and replaced it. System is operating properly at this time.