Performed furnace maintenance on 2004 American standard heater. Upon arrival homeowner stated that system has been working fine and seems to be working even better since we had install the thermostat last visit. Perform safety inspection and maintenance on heater 1. Found that system is not equipped with surge protection in the case of a power outage 2. Flame sensor is in bad condition although was cleaned off at this time recommend that this is replaced to prevent future failure 3. Indoor blower motor was heavily caked woth dust and debris due to washable filter inefficiently stopping dust particles entering into the air mixing cabinet. Dusted motor at this time 4. Recommend disposable Merv eight filters are used and swapped out every 1 to 3 months to keep system cleanly and reduce dust build up. At this time homeowner would like indoor search protector installed to protect the brains of the system and would like a outdoor search protector installed in the summertime. Would also like