Performed AC diagnostic on 2004 York condensing unit. Upon my diagnostic I found that the indoor unit was not blowing air at all. I proceeded outside to verify if the outdoor unit was on but was completely covered in about 3 to 4 inches of ice from the compressor running all the way up the linesets and back to the evaporator coil. This was caused due to the indoor blower failing and not blowing air across the evaporator coil. The system was ran for about a day prior of my arrival without the indoor blower on ultimately resulting in all of this ice. Furnace repairs must take place first before even being able to verify if AC is working. Upon departure system was non-operational and Supervisor will be returning on Tuesday to discuss options for Mrs and Mr Garret. 4 Ton York condenser and Furnace- 1. Indoor blower motor windings overheating and spinning at a Very low rate. Motor has failed. 2. Single run motor controls was completely blown for the fan motor indoor, this was caused due t