41638 Eastman Dr. Suite B
Murrieta, CA 92562
(888) 659-2665

Job Locations
for canyon lake, ca


Map of Canyon Lake CA
Jorge C.

Jorge C.


Job Checkin

Performed diagnostic on 16 year old Ducane system. Homeowner states that system will run for about 15 mins and then the outdoor fan motor will stop spinning and unit will stop cooling. Her dad replaced the capacitor and fixed some electrical and the unit worked for a bit and then started doing the same thing again. Cycled system for cooling. System kicked on and started cooling. After about 15 minutes condenser motor shut off. Motor was extremely hot to the touch and had gone into heat overload. Motor is shot and needs to be replaced. Thoroughly went over entire system to address any other concerns. Wiring at breaker box is not done correctly and wiring is not the correct gauge, and condenser does not have a disconnect box. Homeowner has an electrician coming over the weekend and will have him address those concerns. Secondary motor control was found out of range, and primary motor control was burnt and pitted and had a burnt high voltage wire. Indoor blower wheel is extremely dirty an